Si21-205
FHQ35/50/60BUV1B
Removal Procedure
261
2.5
Removal of Fan Bearing
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the fan rotor
according to the
procedures for removing
the fan rotor and fan
motor.
1
Remove the left side
panel installation screw.
2
Slide the left side panel
toward the front of the
unit and remove.
3
Remove the 2 bearing
installation screws and
remove the bearing.