![background image](http://html1.mh-extra.com/html/daikin/sky-air-b-series-r-410a/sky-air-b-series-r-410a_service-manual_2460071257.webp)
FFQ25/35/50/60BV1B
Si21-205
246
Removal Procedure
1.12 Replacement of Heat Exchanger
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Removing the heat
exchanger
1
Remove the refrigerant
pipe after completion of
refrigerant collection
and pump down
operation.
This work should be
performed with two
personnel including one
person for supporting the
heat exchanger to avoid
falling down during the work.
2
Remove the fixing plate
of heat exchanger.
3
Remove the pipe fixing
plate mounted with two
screws.
4
Remove the heat
exchanger.
(S2675)
Heat exchanger
fixing plate
Pipe fixing
plate
(S2676)
(S2677)