Si21-205
FFQ25/35/50/60BV1B
Removal Procedure
243
4
Insert the float switch
ass'y.
At this time, put the lead
wires in the wiring
groove properly.
5
Install the drain pump
together with the float
switch with screw
and
.
Step
Procedure
Points
(S2661)
Wiring groove
Lead wires
Screw
R
Screw
S
(S2669)
When install the drain
pan, put the lead wires
of float switch and drain
pump in wiring groove
and pass the lead wires
above on the black
sealing material on the
drain pan.
(Otherwise, due
dripping may occur due
to leakage of cool air.)