3
|
Components
Service manual
83
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
a
HAP LED
Does the HAP LED blink in regular
intervals (1 second ON/1 second OFF)?
Action
Yes
Return to
and continue with the next procedure.
No
Replace the inverter PCB, see
89].
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the inverter PCB, see
81].
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.
Is the correct spare part for the
inverter PCB installed?
Action
Yes
Return to
and continue with the next procedure.
No
Replace the inverter PCB, see
89].
To check the wiring of the inverter PCB
Prerequisite:
First perform all earlier checks of the inverter PCB, see
81].
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
135].
2
Check that all wires are properly connected and that all connectors are fully
plugged‑in.