3
|
Components
Service manual
66
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
a
Connector X101A
4
Check the wiring from pins 2 and 3 of connector X101A to the current sensor.
5
Disconnect the current sensor connector from the connector X101A on the
main PCB and measure the resistance between pins 2 and 3 of the current
sensor connector.
Result:
The measured value MUST be 45~50 Ω.
Is the measured resistance correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the current sensor, see
3.3.2 Repair procedures
To remove the current sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
111].
1
Disconnect the current sensor connector from the connector X101A on the
main PCB.