3
|
Components
Service manual
71
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
a
Expansion valve motor
2
Pull the expansion valve motor to remove it from the expansion valve body.
INFORMATION
It may be needed to turn the expansion valve coil 1/8 turn counter clockwise to
unlock it. Make sure to note the correct orientation (position) of the expansion valve
coil before removal.
3
Cut all tie straps that fix the expansion valve motor harness.
4
Disconnect the expansion valve motor connector (X21A for main expansion
valve Y1E and X22A for injection expansion valveY2E) from the main PCB.
5
To install the expansion valve motor, see
70].
To remove the expansion valve body
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
Prerequisite:
If needed, remove any parts or insulation to create more space for
the removal.
1
Remove the expansion valve motor, see
70].
2
Cut the expansion valve pipes using a pipe cutter.