3
|
Components
Service manual
93
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
b
b
a
a
c
a
Screw
b
Bracket
c
Clip
3
Disconnect the low pressure switch connector from the appropriate PCB.
4
Cut all tie straps that fix the low pressure switch harness.
a
b
a
Low pressure switch
b
Low pressure switch pipe
5
Cut the low pressure switch pipe using a pipe cutter.
6
Remove the low pressure switch from the unit.
7
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
8
Heat the end of the low pressure switch pipe using an oxygen acetylene torch
and remove the low pressure switch pipe end.
9
Stop the nitrogen supply when the piping has cooled down.
10
To install the low pressure switch, see
To install the low pressure switch
1
Install the low pressure switch in the correct location.