2
|
Troubleshooting
Service manual
17
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
If…
Then…
Remote controller is defective
Emergency operation can be used to go
to cooling or heating. In emergency
operation, the compressor is forced to
operate until the defective indoor or
outdoor unit PCB is back online.
Indoor unit PCB is defective
Outdoor unit PCB is defective
Starting conditions
In case the customer strongly needs the heating/cooling operation while waiting
for the next service visit, you can manually operate the system by changing the
emergency switch on the indoor unit and outdoor unit PCB from "normal" to
"emergency". When emergency operation is active, the system CANNOT control
the room temperature.
Both the indoor and outdoor unit MUST be set to "emergency" while the power is
OFF.
Ending conditions
You can end the emergency operation by changing the emergency switch on the
indoor unit and outdoor unit PCB back to "normal" while the power is OFF.
Below table explains what will happen when the emergency switch is set to
"emergency":
Changing the emergency switch on
the…
Switches ON the…
Indoor unit
▪
Indoor unit fan
▪
Drain pump
Outdoor unit
▪
Compressor
▪
Outdoor unit fan
Activate emergency operation
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Set the emergency switch on the indoor unit PCB to the "emergency" position,
see indoor unit service manual for more information.
2
Set the emergency DIP switch DS1‑1 on the outdoor unit PCB to the "ON"
position.
EMERGENCY
ON
COOL
OFF
HEAT
EMERGENCY
ON
COOL
OFF
HEAT
a b
a b
a
DS1‑1
b
DS1‑2
EMERGENCY
Emergency
ON
On
OFF
Off