4
|
Third party components
Service manual
136
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
2
Measure the voltage on the unplugged rectifier voltage check connector X3A.
Result:
The measured voltage MUST be below 10 V DC.
a
a
Connector X3A
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding.
To check the wiring between the outdoor unit and the indoor unit
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
151].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.