Troubleshooting
Service manual
26
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Possible cause:
Faulty expansion valve.
7
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
8
Perform
a
check
of
all
refrigerant
side
thermistors.
See
Possible cause:
Faulty refrigerant side thermistor(s).
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.4.10 H3-00 – Outdoor unit: Malfunction of high pressure switch
Trigger
Effect
Reset
High pressure switch is
activated when
compressor is off.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the high pressure switch. See
78].
Possible cause:
Faulty high pressure switch.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
3
Check if the power supply is conform with the regulations. See
135].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.4.11 H4-00 – Low pressure switch abnormality
Trigger
Effect
Reset
When there is no
continuity in the low
pressure switch during
compressor start.
Unit will stop operating.
Automatic reset.