2
|
Troubleshooting
Service manual
44
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Check
Detail
Check the internal leakage of the 4‑way
valve
▪
After
compressor
running
for
10 minutes, is there a temperature
difference between the suction pipe
and the discharge pipe?
▪
Is the pressure difference between
the internal service port (small) and
the gas pipe service port sufficient
(>0.3MPa)?
2.5.4 Operating noise and vibrations
Check
Detail
Check the installation conditions
(specified in the installation manual).
▪
Use general vibration prevention
where needed.
▪
If the mounting wall is too thin, you
must use cushion material or rubber,
or change the installation place.
▪
Refrigerant piping is too short; is the
length within specified range?
▪
Due to bad installation or general
conditions there may be deformation
of the unit.
▪
Are all the screws installed and
tightened properly?
▪
Is all piping secured, fixed and
supported by inserting a cushion
material where needed?
▪
Install piping weights or correct by
hand if any piping is in contact with
other parts.
▪
Is the fan in contact with other parts?
If so separate the fan from the other
parts.
Check refrigerant charge.
▪
Is the unit filled with the specified
refrigerant volume?
▪
Is there a flushing noise, due to
refrigerant shortage?
▪
Is there air in the system?
Check the expansion valve.
If a passing sound is heard from the
pressure reducing valve, apply sound
insulation sheets of putty to reduce the
valve noise.