3
|
Components
Service manual
57
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
To perform a mechanical check of the compressor
Prerequisite:
First perform an auditive check of the compressor, see
56].
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
2
Check the compressor dampers and piping for any damage.
a
a
1
Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers and piping are in
a good condition?
Action
Yes
Perform an electrical check of the
compressor, see
No
Replace the compressor, see
61].
To perform an electrical check of the compressor
1
First perform a mechanical check of the compressor, see
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
135].
2
Remove the cover of the compressor wire terminals.
Summary of Contents for Sky Air Advance RZA200D7Y1B