3
|
Components
Service manual
117
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
a
Thermal interface grease on heat sink
3
Install the switch box on the correct location in the outdoor unit. Take the
following into account:
▪
Route the DC fan motor harness in front of the switch box to easily connect
it later on.
▪
Route the compressor wiring harness (Faston connectors) downwards
between the compressor body and the discharge pipe.
▪
Guide the sheet metal plate of the service port behind the switch box
mounting plate to correctly install the service port and avoid pipe bending.
▪
Slightly tilt the heat sink forward (±10°) and avoid that the thermal interface
grease gets smeared everywhere.
▪
Hook the switch box mounting plate in the support plate on the right hand
side.
4
Install the hooks of the switch box supporting plate in the openings of the
switch box.
a
b
a
c
a
Screw
b
Switch box supporting plate
c
Switch box
5
Install and tighten the 2 screws to fix the switch box supporting plate to the
unit.