3
|
Components
Service manual
130
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
–9
–8
–7
–6
–5
–4
–3
–2
–1
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
21
22
23
24
25
26
27
28
29
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
51
52
53
54
55
56
57
58
59
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
0
65.84
30
16.10
60
4.87
1
2
3
4
5
6
7
8
9
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
31
32
33
34
35
36
37
38
39
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
61
62
63
64
65
66
67
68
69
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
Type 2 thermistor
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
0
5
10
15
20
25
30
35
635.1
496.6
391
310
247.3
198.5
160.2
130.1
40
45
50
55
60
65
70
75
106.2
87.1
71.8
59.5
49.5
41.4
34.8
29.3
80
85
90
95
100
105
110
115
24.9
21.1
18
15.4
13.3
11.4
9.9
8.6
120
125
130
135
140
145
150
7.5
6.5
5.7
5
4.4
3.9
3.4
Type 3 thermistor
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
0
10
20
30
40
806.5
478.8
292.9
184.1
118.7
50
60
70
80
90
78.3
52.8
36.3
25.4
18.1
100
110
120
130
140
13.1
9.6
7.1
5.4
4.1
150
160
170
180
3.2
2.5
1.9
1.5
5
Disconnect the thermistor connector from the appropriate PCB.
6
Measure the resistance between the appropriate pins of the thermistor
connector.