4
|
Third party components
Service manual
144
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Service tool
Remark
Scale
Read-out / 10 grams
Manifold
Compatible with the
refrigerant to be
recovered
Flexible hoses
Compatible with the
refrigerant to be
recovered
Recovery cylinder
Compatible with the
refrigerant to be
recovered
Vacuum pump
2-stage, equipped with
solenoid valve
2
Setup a vacuum line between recovery unit discharge and the recovery bottle.
Without this additional setup, the discharge line from the recovery device to
the refrigerant cylinder would not have been vacuumed.
3
Connect the vacuum pump, manifold, recovery unit, and refrigerant recovery
cylinder to the service ports of the refrigerant circuit as shown below.