2
|
Troubleshooting
Service manual
34
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
2.4.22 L9-00 – Stall prevention time lag
Trigger
Effect
Reset
Outdoor unit inverter PCB
detects compressor
overload at start‑up.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the compressor. See
Possible cause:
Faulty compressor.
2
Check if the power supply is conform with the regulations. See
135].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
3
Perform a check of the inverter PCB. See
Possible cause:
Faulty inverter PCB.
4
Check that all stop valves of the refrigerant circuit are open. See
137].
Possible cause:
Closed stop valve in the refrigerant circuit.
5
Check if the refrigerant circuit is clogged. See
137].
Possible cause:
Clogged refrigerant circuit.
6
Check if the refrigerant circuit is correctly charged. See
137].
Possible cause:
Refrigerant overcharge or shortage.
7
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.4.23 LC-00 – Malfunction in communication system of outdoor unit
Trigger
Effect
Reset
No transmission between
the outdoor unit main
PCB and the outdoor unit
inverter PCB.
Unit will stop operating.
Automatic reset.