The Fan Inlet and exhaust must be kept clear of obstructions. Failure to keep the Fan airflow path
clear of obstructions could cause loss of Fan perfomance and Fan damage.
48" and 52" Hyflo
TM
Fans
Installation and Operators Instruction Manual
Fan and Fan Framing Dimensions
MV17 47 - 01 6 0 4/ 03
Item
48" Hyflo
52" Hyflo
1
41-7/8" [106.36 cm]
44" [111.76 cm]
2
59" [149.9 cm]
64" [162.56 cm]
3
5-1/8" [13.02 cm]
5-1/8" [13.02 cm]
4
12.35" [31.37 cm]
12.35" [31.37 cm]
5
2-5/16" [5.87 cm]
4-1/8" [10.48 cm]
3
2
Figure 1. Fan Dimensions
4
1
5
MV1747-017 04/03
3
2
3
2
Planning the layout of the spacing between Fans is very important.
Spacing too close together will cause interference between the
discharge Cones.
The Rough Opening dimensions for Fans are
shown above
.
Item
48" Hyflo
52" Hyflo
1
4" [10.16 cm] Minimum
8" [20.32 cm] Minimum
2
55" [139.7 cm]
56-1/2" [143.51 cm]
3
1
MV1747D
July 2003
Do Not
operate these Fans with a variable speed control device. Operating static pressure should be less
than 0.15 inches water column.