4
|
Third party components
Service manual
138
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
b
a
Liquid stop valve
b
Gas stop valve
2
Check if the stop valves are completely open.
The refrigerant circuit stop valves are
open?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Open the stop valves of the refrigerant
circuit, see
To check if the refrigerant circuit is clogged
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Wait for the refrigerant to reach the outdoor temperature.
2
Connect a manometer to the high pressure and low pressure service ports.
3
Turn ON the power of the unit.
4
Activate
Heating
operation via the user interface.
5
Read the pressure on the high and low pressure gauges. If there is a significant
difference between high and low pressure, the refrigerant circuit might be
clogged.
6
On the refrigerant liquid piping (between the indoor unit heat exchanger and
the outdoor unit heat exchanger (coil)), using a contact thermometer,
measure the temperature before and after every restricting device. If a big
temperature difference is measured (>2.5~4K), an internal pipe obstruction
may be present at this location.
INFORMATION
Focus on positions with a potential risk for clogging such as:
▪
Filters
▪
Valves
▪
Brazing points
▪
…