4
|
Third party components
Service manual
142
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
3
Measure the pressure of the refrigerant. The measured pressure converted
into saturated temperature MUST be in line with the expected pressure /
saturated temperature at current ambient temperature.
4
If the measured pressure is significantly higher (>5K), non‑condensables
gasses are most likely present in the refrigerant.
Any non‑condensables found in the
refrigerant circuit?
Action
Yes
To replace the refrigerant, see
142].
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To perform a pressure test of the refrigerant circuit
1
Perform a pressure test in line with local legislation.
CAUTION
Perform a pressure test only when leaks are expected.
Is the pressure in the refrigerant circuit
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the leaking part of the
refrigerant circuit, see
To check if the refrigerant field piping is conform with the regulations
1
Check if the refrigerant field piping is conform with the regulations. Adjust as
needed. See installation manual for field piping specifications.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.2.2 Repair procedures
To open the stop valves of the refrigerant circuit
Prerequisite:
Remove the required plate work, see
111].
1
Remove the caps.