Troubleshooting
Service manual
21
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Possible cause:
Faulty outdoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.4.4 E4-00 – Abnormal suction pressure
Trigger
Effect
Reset
Refrigerant suction
pressure is too low for
5 minutes.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
suction
pipe
thermistor.
See
128].
Possible cause:
Faulty suction pipe thermistor or connector fault.
2
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
3
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
4
Check for the presence of humidity in the refrigerant circuit. See
Possible cause:
Humidity in the refrigerant circuit.
5
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
6
Perform a check of all expansion valves. See
68].
Possible cause:
Faulty expansion valve.
7
Check the required space around the outdoor unit heat exchanger. See
147].
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.
8
Clean the outdoor heat exchanger. See
149].
Possible cause:
Dirty outdoor heat exchanger.
9
Perform a check of the main PCB. See
95].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.