3
|
Components
Service manual
75
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Is the measured output voltage on the
inverter PCB correct?
Action
Yes
Correct the wiring between the fan
inverter PCB and the inverter PCB, see
No
Perform a check of the inverter PCB,
see
To check the HAP LED of the fan inverter PCB
1
First perform a power check of the fan inverter PCB, see
2
Locate the HAP LED on the fan inverter PCB.
a
a
HAP LED
Does the HAP LED blink in regular
intervals (approximately 1 Hz)?
Action
Yes
Return to
PCB and continue with the next
procedure.
No
Replace the fan inverter PCB, see
78].
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the fan inverter PCB, see
74].
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.
Is the correct spare part for the fan
inverter PCB installed?
Action
Yes
Return to
PCB and continue with the next
procedure.
No
Replace the fan inverter PCB, see
78].
Summary of Contents for Sky Air Advance RZA200D7Y1B
Page 1: ...Service manual Sky Air Advance series RZA200D7Y1B RZA250D7Y1B ...
Page 190: ......
Page 191: ......
Page 192: ...ESIE19 13A 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...