3
|
Components
Service manual
74
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
WARNING
When reconnecting a connector to the PCB, do NOT apply force, as this may damage
the connector or connector pins of the PCB.
4
Fix the expansion valve motor harness using new tie straps.
5
Install the insulation cap on the expansion valve motor (if applicable).
Is the problem solved?
Action
Yes
No further actions required.
No
68] of the expansion
valve and continue with the next
procedure.
3.5 Fan inverter PCB
3.5.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the fan inverter PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
111].
Prerequisite:
Access the back side of the switch box, see
1
Turn ON the power of the unit.
2
Measure the voltage between pins 1 and 3 of connector X5A The measured
voltage MUST be 18 V DC.
a
b
a
Pin 1
b
Pin 3
Is the measured voltage on the PCB
correct?
Action
Yes
74] of the PCB and
continue with the next procedure.
No
Continue with the next step.
3
Measure the output voltage voltage on connector X601A on the inverter PCB.
Result:
The measured voltage MUST be 18 V DC.