Third party components
Service manual
143
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
b
a
Liquid stop valve
b
Gas stop valve
2
Completely open the stop valves by screwing the stop valve screw
counterclockwise.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To replace the clogged/leaking part of the refrigerant circuit
1
See the correct procedure for the component that needs to be repaired. See
also
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To recuperate the refrigerant
Prerequisite:
Stop the unit operation via the user interface.
1
Necessary tools:
Service tool
Remark
Refrigerant recovery unit
Compatible with the
refrigerant to be
recovered