2
|
Troubleshooting
Service manual
29
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
2.4.15 J6-00 – Outdoor unit: Malfunction of heat exchanger thermistor
Trigger
Effect
Reset
Outdoor heat exchanger
thermistor input is out of
range.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
heat
exchanger
thermistor.
See
128].
Possible cause:
Faulty heat exchanger thermistor.
2
Perform a check of the main PCB. See
95].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.4.16 J7-00 – Outdoor unit: Intermediate heat exchanger thermistor abnormality
Trigger
Effect
Reset
Heat exchanger (middle)
thermistor detects an
abnormal value (open or
short circuit).
Unit will stop operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the heat exchanger (middle) thermistor. See
128].
Possible cause:
Faulty heat exchanger (middle) thermistor.
2
Perform a check of the main PCB. See
95].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.