Sky Air Advance-series
ESIE19-13A – 2020.05
Overview of field settings for indoor units
The overview lists the field settings for the indoor unit FCAG-B. For more detailed field settings and field settings of
other indoor units, see service manual of the indoor units.
Bold content is default setting
.
Mode
1
st
code
Description function
2
nd
code
Description selection
10(20)
0
Filter cleaning sign interval / Long
life filter
01
2500 hr
02
1250 hr
1
Filter type
01
Long
02
Super long
2
Remote controller thermistor
01
Enabled
02
Disabled
3
Filter cleaning sign
01
Display
02
No display
7
(3)
Detection time for NOT presence
01
30 minutes
02
60 minutes
8
(4)
Compensation of suction air
temperature in heating mode
01
COMPENSATE
Temperature [A+2]°C which an air
conditioner controls when the
temperature of a remote
controller is A°C)
02
NO COMPENSATION
Temperature [A]°C which an air
conditioner controls when the
temperature of a remote
controller is A°C)
11(21)
2
Fan OFF at thermostat OFF
01
Normal
02
OFF
3
Airflow rate setting during
heating
01
Standard
02
Slight up
03
Up
4
Automatic operation mode
control
01
Available
02
Prohibition
6
(5)
Sensitivity of presence sensor
01
High
02
Low
03
Standard
04
Sensor does not work