3
|
Components
Service manual
103
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
b
c
a
L1B
b
L2B
c
L3B
Is the output voltage on the noise filter
PCB correct?
Action
Yes
Return to
101] of the noise filter
PCB and continue with the next
procedure.
No
Replace the noise filter PCB, see
105].
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the noise filter PCB, see
101].
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.
Is the correct spare part for the noise
filter PCB installed?
Action
Yes
Return to
101] of the noise filter
PCB and continue with the next
procedure.
No
Replace the noise filter PCB, see
105].
To check the wiring of the noise filter PCB
Prerequisite:
First perform all earlier checks of the noise filter PCB, see
101].
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.