Chapter 12 Cisco ASR 1001 Router Overview and Installation
Attaching a Chassis Ground Connection
Step 1
Align the cable-management bracket to the rack-mount bracket on one side of the Cisco ASR 1001
Router. The cable-management bracket aligns to the top hole of the chassis rack-mount bracket.
Step 2
Using a Phillips screwdriver, insert the screw through cable-management bracket and into the chassis
rack-mount and tighten the screw.
Note
Use the package of screws that came with your chassis containing four screws.
Figure 12-18
shows where to attach the front rack-mount brackets to the Cisco ASR 1001 Router in a
rack.
Figure 12-18
Chassis Rack-Mount Bracket Ear Holes for the Cable-Management Bracket
Step 3
Using the bottom rack-mount ear hole, insert the screw through cable-management bracket and into the
chassis rack-mount (see
Figure 12-18
).
This completes the procedure for installing the cable-management brackets on the chassis.
Attaching a Chassis Ground Connection
Connecting the Cisco ASR 1000 Series Router to ground is required for all DC powered installations
and any AC powered installation where compliance with Telcordia grounding requirements is necessary.
Caution
The dual-lug chassis stud must be installed, the SIP and SPA must be fully inserted and screwed in and
earthed to prevent a potential hazard in a telecom line.
Have the recommended tools and supplies available before you begin this procedure.
1
Secure the cable-management screw to the middle ear hole of the front rack-mount bracket on
both sides of the Cisco ASR 1001 Router.
1
1