6-23
Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
OL-13208-11
Chapter 6 Cisco ASR 1006 Router Overview and Installation
Connecting Power to the Cisco ASR 1006 Router
•
Use a crossover cable to connect to an MDI port
•
Use a straight-through cable to connect to an MDI-X port
Connecting Power to the Cisco ASR 1006 Router
Warning
The covers are an integral part of the safety design of the product. Do not operate the unit without the
covers installed.
Statement 1077
Warning
When you install the unit, the ground connection must always be made first and disconnected last.
Statement 1046
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Statement 1030
This section describes the procedure to connect AC input and DC input power to your Cisco ASR 1006
Router.
The DC power supply for the Cisco ASR 1006, ASR 1004, ASR 1002, and ASR 1013 routers operate at
individual specifications.
Table 6-2
shows the common input ranges and circuit breaker requirements.
Power Cords Supported by the Cisco ASR 1006 Router
The following power cords are supported by the Cisco ASR 1006 Router:
•
CAB-AC20A-90L-IN—20 A AC right-angle power cord—International
•
CAB-4000W-US1—Power cord, 250 VAC 20 A, Right Angle C19, NEMA 6-20 Plug, US
Table 6-2
Cisco ASR 1000 Series Router DC Power Supply System Input Requirements
Cisco ASR 1000
Series Router DC
Power Supply
System Input Rating (Amps)
Circuit Breaker Amps
AWG # Wire
Minimum
Maximum
Minimum
Maximum
Cisco ASR 1006
40
Always 50
Always AWG #6 wire
Cisco ASR 1004
24
30
40
10
8
Cisco ASR 1002
16
20
30
12
10
Cisco ASR 1013
40
Always 50
Always AWG #6 wire
For example, the Cisco ASR 1002 Router DC power supply, with 16 Amp input rating must use an AWG #12 gauge wire for a 20 A circuit breaker and
an AWG #10 gauge wire for a 30 A circuit breaker.