Monitor and control equipment
74
i-Vu CCN Pro 4.2
3
Click
Alarms
.
4
To edit an existing alarm category, select the alarm under
Select Category
and edit the
Category Name
,
Reference Name
, or
Icon
. See table below.
5
To add a new category, click
Add
. See table below.
6
Click OK.
Field
Notes
Reference
Name
Must be unique in the database, be lowercase, and not contain any spaces.
Icon
Find or create a 32 x 32 pixel icon (.gif file) that represents the new category.
For example,
Store the .gif file in the
i-Vu CCN Prox.x\webroot\_common\lvl5\
graphics\event_categories
folder.
Type
/_common/lvl5/graphics/event_categories/<file_name>.gi
f
in the
Icon
field.
Trends
i-Vu CCN Pro can read and store equipment status values over time and then display this information in a
graph to help you monitor the equipment’s operation.
Trends are automatically enabled for points that appear on equipment graphics (if the graphic was generated
from the i-Vu CCN Pro Library). Samples are automatically collected every 20 minutes.
An unlimited amount of trend data can be collected for any input or output point in i-Vu CCN Pro. Trends can
be generated for individual points or multiple points on one graph.
To collect trend data for a point
Before you can look at a trend graph for a point, you must enable trending for that point and then tell i-Vu
CCN Pro how you want the controller to collect the point's data.
1
On the navigation tree, select the equipment that has the point you want to trend.
2
Click the
Trends
button drop-down arrow, select
Enabled
or
Disabled Points
, then select the point.
3
Click the
Enable/Disable
tab, then verify that
Enable Trend Log
is checked.
4
Enter information in the appropriate fields. See table below.
5
Click
OK
.
TIP
You can set up all trends for a piece of equipment at once on the
Trend Sources
tab of the equipment's
Properties
page.