Reset Parameters to Factory Settings
Sometimes it is necessary to restore the parameter values to the factory settings. Follow
this procedure to do so. Be sure to change the Level 2 Motor Data block “Motor Rated
Amps” to the correct value after this procedure (restored factory setting is 999).
Note: All specific application parameters already programmed will be lost when
resetting the control to factory settings.
Note: After factory settings are restored, the drive must be auto tuned.
Action
Description
Display
Comments
Apply Power
Keypad Display shows this
opening message.
Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation.
Display mode. Stop LED on.
Press PROG key
Enter program mode.
Press
Y
or
B
key
Scroll to Level 2 Blocks.
Press ENTER key
Select Level 2 Blocks.
Press
Y
or
B
key
Scroll to the Miscellaneous block.
Press ENTER key
Select Miscellaneous block.
Press
Y
key
Scroll to Factory Settings
parameter.
Press ENTER key
Access Factory Settings
parameter.
V
represents blinking cursor.
Press
Y
key
Scroll to YES, to choose original
factory settings.
Press ENTER key
Restores factory settings.
“Loading Presets” is first message
“Operation Done” is next
“No” is displayed last.
Press
Y
key
Scroll to menu exit.
Exit Level 2 blocks.
Press
Y
or
B
key
Scroll to Programming exit.
Exit Programming mode and
return to Display mode.
Press ENTER key
Return to display mode.
Display mode. Stop LED on.