Section 1
General Information
B-2 Appendix B
MN718
Table B-1 Parameter Block Values Level 1
Continued
Level 1 Blocks - Continued
Block Title
Parameter
P#
Adjustable Range
Factory
User
Setting
INPUT
OPERATING MODE
1401
KEYPAD
STANDARD RUN
15SPD
FAN PUMP 2 WIRE
FAN PUMP 3 WIRE
SERIAL
BIPOLAR
PROCESS MODE
KEYPAD
COMMAND SELECT
1402
POTENTIOMETER
+/-10 VOLTS
+/-5 VOLTS
4 TO 20 mA
10V W/ TORQ FF
EXB PULSE FOL
5V EXB
10 V EXB
4-20mA EXB
3-15 PSI EXB
TACHOMETER EXB
SERIAL
NONE
+/-10
VOLTS
ANA CMD INVERSE
1403
OFF, ON
OFF
ANA CMD OFFSET
1404
-20.0 TO +20.0%
(where
±
0.5V=
±
20%)
0.0 %
ANA 2 DEADBAND
1405
0-10.00 V
0.00 V
ANA 1 CUR LIMIT
1406
OFF, ON
OFF
OUTPUT
OPTO OUTPUT #1
1501
READY
ZERO SPEED
AT SPEED
AT SET SPEED
READY
OPTO OUTPUT #2
1502
AT SET SPEED
OVERLOAD
KEYPAD CONTROL
FAULT
FOLLOWING ERR
ZERO
SPEED
OPTO OUTPUT #3
1503
FOLLOWING ERR
MOTR DIRECTION
DRIVE ON
CMD DIRECTION
AT POSITION
AT SPEED
OPTO OUTPUT #4
1504
AT POSITION
OVER TEMP WARN
PROCESS ERROR
DRIVE RUN
FAULT
ZERO SPD SET PT
1505
0-MAX Speed
200 RPM
AT SPEED BAND
1506
0-1000 RPM
100 RPM
SET SPEED
1507
0-MAX Speed
Rated Motor
Speed