Section 1
General Information
B-4 Appendix B
MN718
Table B-2 Parameter Block Values Level 2
Level 2 Blocks
Block Title
Parameter
P#
Adjustable Range
Factory
User
Setting
OUTPUT LIMITS
OPERATING ZONE
2001
STD CONST TQ
STD VAR TQ
QUIET CONST TQ
QUIET VAR TQ
STD
CONST TQ
MIN OUTPUT SPEED
2002
0-MAX Speed
0 RPM
MAX OUTPUT SPEED
2003
0-32767 RPM
Rated Motor
Speed
PK CURRENT LIMIT
2004
0-PEAK RATED CURRENT
PK Control
Rating
PWM FREQUENCY
2005
1.0-5.0 KHZ (Standard)
1.0-16.0 KHZ (Quiet)
2.5 KHZ
CUR RATE LIMIT
2006
0-10.00 SEC
0.000 SEC
CUSTOM UNITS
DECIMAL PLACES
2101
0-5
5
VALUE AT SPEED
2102
0-65535 / 0-65535
00000/
01000 RPM
UNITS OF MEASURE
2103
Selection of 9 Character Sets
-
PROTECTION
OVERLOAD
2201
FAULT, FOLDBACK
FOLDBACK
EXTERNAL TRIP
2202
OFF, ON
OFF
LOCAL ENABLE INP
2203
OFF, ON
OFF
FOLLOWING ERROR
2204
OFF, ON
OFF
TORQUE PROVING
2205
OFF, ON
OFF
MISCELLANEOUS
RESTART AUTO/MAN
2301
AUTOMATIC, MANUAL
MANUAL
RESTART FAULT/HR
2302
0-10
0
RESTART DELAY
2303
0-120 SECONDS
0 SEC
FACTORY SETTINGS
2304
YES, NO
NO
HOMING SPEED
2305
0-MAX Speed
100 RPM
HOMING OFFSET
2306
0-65535 CNTS
Encoder
Counts
SECURITY
CONTROL
SECURITY STATE
2401
OFF
LOCAL SECURITY
SERIAL SECURITY
TOTAL SECURITY
OFF
ACCESS TIMEOUT
2402
0-600 SEC
0 SEC
ACCESS CODE
2403
0-9999
9999
MOTOR DATA
MOTOR VOLTAGE
2501
0-999 VOLTS
Factory Set
MOTOR RATED AMPS
2502
0-999.9
Factory Set
MOTOR RATED SPD
2503
0-32767 RPM
1750 RPM
MOTOR RATED FREQ
2504
0-1000 Hz
60.0 Hz
MOTOR MAG AMPS
2505
0-85% Rated Current
CALC
ENCODER COUNTS
2506
50-65535 CNTS
1024 PPR
RESOLVER SPEEDS
2507
0 to 10
0 SPEED
CALC PRESETS
2508
YES, NO
NO
Summary of Contents for 18H Series
Page 1: ...SERIES 18H AC Flux Vector Control Installation Operating Manual 9 97 MN718 VECTOR DRIVE ...
Page 105: ...Section 1 General Information 5 18 Troubleshooting MN718 ...
Page 109: ...Section 1 General Information 6 4 Manual Tuning the Series 18H Control MN718 ...
Page 144: ...Appendix C Appendix C 1 MN718 ...