Section 1
General Information
B-6 Appendix B
MN718
Table B-2 Parameter Block Values Level 2
Continued
Level 2 Blocks - Continued
Block Title
Parameter
P#
Adjustable Range
Factory
User
Setting
COMMUNICATIONS
PROTOCOL
2801
RS–232 ASCII, RS-485 ASCII
RS–232
ASCII
BAUD RATE
2802
9600, 19.2KB, 38.4KB, 57.6KB,
115.2KB, 230.4KB
9600
DRIVE ADDRESS
2803
0 - 31
0
AUTO-TUNING
CALC PRESETS
2508
YES, NO
NO
CMD OFFSET TRM
Measures and trims out
offset voltage at Analog
Input #2 (J1-4 & J1-5).
AU1
-
-
CUR LOOP COMP
Measures current
response while running
motor at one half the rated
motor current.
AU2
-
-
STATOR R1
Measures stator resistance
AU3
-
-
FLUX CUR SETTING
Sets the Motor Mag Amps.
AU4
-
-
FEEDBACK TESTS
Checks the Master
Encoder and Feedback
Align values.
AU5
-
-
SLIP FREQ TEST
Measures motor Slip
Frequency during motor
acceleration/deceleration
at repeated intervals.
AU6
-
-
SPD CNTRLR CALC
Measures the motor
current to acceleration
ratio during motor rotation.
This procedure adjusts the
Speed INT Gain and
Speed PROP Gain
parameters.
AU7
-
LEVEL 1 BLOCK
Enters Level 1 Menu - See Table B-1.
Exit programming mode and return to display mode.
Summary of Contents for 18H Series
Page 1: ...SERIES 18H AC Flux Vector Control Installation Operating Manual 9 97 MN718 VECTOR DRIVE ...
Page 105: ...Section 1 General Information 5 18 Troubleshooting MN718 ...
Page 109: ...Section 1 General Information 6 4 Manual Tuning the Series 18H Control MN718 ...
Page 144: ...Appendix C Appendix C 1 MN718 ...