3-14 Receiving & Installation
MN718
Tap Change Procedure (size G controls). See Figure 3-2.
1.
Be sure drive operation is terminated and control is disabled.
2.
Remove all power sources from the control. If power has been applied, wait at
least 5 minutes for bus capacitors to discharge.
3.
Remove or open the front cover.
4.
Remove the wires from the two right side terminals.
5.
Place the wires on the center terminals as shown.
6.
Install or close the front cover.
Figure 3-2 Configuring the Control Transformer Terminal Block for 380 - 400 VAC (Size G)
460VAC
380-400VAC