10 Safety instructions
Manual Energy Storage Inverter ESI-S
WARNING: If the ground is not done properly, under certain fault conditions in the unit
or in the system to which it is connected it can result in full line voltage between
chassis and earth ground. Severe injury or death can result if the chassis and earth
ground are touched simultaneously.
WARNING: The neutral current in an ESI-S inverter may be as high as 3 times the line
current hence do not use a 4 pole breaker to connect this type of inverter as the rating
of the neutral pole may not be adequate.