Manual Energy Storage Inverter ESI-S
The ESI-Manager user interface 127
Above 40°C (104°F), the maximum output current must be derated by 3.5% every
additional 1°C (1.8°F) up to 50°C (122°F) maximum limit.
The total required derating is the sum of all the deratings taking into account the
installation height and the ambient temperature.
The ESI-Manager rating menu shows the inverter nominal rating, which is by default
100%. The new value to be set when derating is required is 100% - (total required
derating %).
After approving the new rating value (
), the inverter will reset and the new value will
be taken into account. In practice, this implies that the output current of the unit will be
limited to the inverter nominal current times the entered rating factor. E.g. a rating
factor of 50% implies that the maximum RMS inverter current is half the nominal inverter
current.
Pressing
will result in the original value being restored and the inverter rating
menu being quit.
7.9.3.6 Setting up the user’s requirements
For entering the user’s requirements at the commissioning level, go to
[/Welcome/Settings/Commissioning/User]
At the commissioning level, a shortcut exists to the principal user set up menus. These
consist of: