Parameters 295
Displays the torque controller limitation status word.
This parameter is read-only.
-
0000h…FFFFh
Torque limitation status word.
1 = 1
Defines the minimum allowed speed.
WARNING!
This value must not be higher than
.
WARNING!
In frequency control mode, this limit is not
effective. Make sure the frequency limits (
) are set appropriately if frequency control is
used.
WARNING!
In a master/follower configuration, do not
set maximum and minimum speed limits with the
same sign on a follower drive. See section
(page
-1500.00
rpm;
-1800.00 rpm
(
b0)
-30000.00 …
30000.00 rpm
Minimum allowed speed.
See par.
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Undervoltage
*1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum torque *1 = Torque is being limited by
,
or the source of
. See
diagram on page
3
Maximum torque *1 = Torque is being limited by
,
or the source of
See diagram on page
4
Internal current
1 = An inverter current limit (identified by bits 8…11) is active
5
Load angle
(With permanent magnet motors and synchronous reluctance motors
only)
1 = Load angle limit is active, ie. the motor cannot produce any more
torque
6
Motor pullout
(With asynchronous motors only)
1 = Motor pull-out limit is active, ie. the motor cannot produce any
more torque
7
Reserved
8
Thermal
1 = Input current is being limited by the main circuit thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being limited
10
User current
*1 = Output current is being limited by
11
Thermal IGBT
*1 = Output current is being limited by a calculated thermal current
value
12
IGBT
overtemperature
*1 = Output current is being limited because of estimated IGBT
temperature
13
IGBT overload
*1 = Output current is being limited because of IGBT junction to case
temperature
14…15 Reserved
*Only one out of bits 0…3, and one out of bits 9…13 can be on simultaneously. The bit typically
indicates the limit that is exceeded first.
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...