Parameters 179
User-defined control word 2.
-
0000h…FFFFh
User-defined control word 2.
1 = 1
(Only visible when IGBT supply unit control activated by
Drive status word 1 received from the supply unit.
See also section
Control of a supply unit (LSU)
(page
and parameter group
This parameter is read-only.
-
0000h…FFFFh
Drive status word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
User control word 2 bit 0
User-defined bit.
1
User control word 2 bit 1
User-defined bit.
…
…
…
15
User control word 2 bit 15 User-defined bit.
Bit
Name
Description
0
Enabled
1 = Run enable and start enable signals are present
1
Inhibited
1 = Start inhibited
2
Operation
allowed
1 = Drive is ready to operate
3
Ready to start 1 = Drive is ready to receive a start command
4
Running
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being controlled)
7
Limiting
1 = Any operating limit is active
8
Local control
1 = Drive is in local control
9
Network
control
1 = Drive is in network control
10
Ext1 active
1 = Control location Ext1 active
11
Ext2 active
1 = Control location Ext2 active
12
Charging relay 1 = Charging relay is closed
13
MCB relay
1 = MCB relay is closed
14…15 Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...