![ABB ACS880-01 Series Firmware Instructions Download Page 315](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621315.webp)
Parameters 315
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
Selects the action the drive takes when the value monitored
by signal supervision 3 exceeds its limits.
Note:
This parameter does not affect the status indicated by
.
No action
No action taken.
0
Warning
A warning (
) is generated.
1
Fault
The drive trips on
.
2
Fault if running
If running, the drive trips on
3
Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter
Defines a filter time constant for the signal monitored by
signal supervision 3.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 3.
0.00
-21474830.00 …
21474830.00
Low limit.
-
Defines the upper limit for signal supervision 3.
0.00
-21474830.00 …
21474830.00
Upper limit.
-
33
Configuration of maintenance timers/counters.
See also section
Maintenance timers and counters
(page
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have exceeded
their limits.
This parameter is read-only.
-
0000 0000b …
0011 1111b
Maintenance time/counter status word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
On-time1
1 = On-time timer 1 has reached its preset limit.
1
On-time2
1 = On-time timer 2 has reached its preset limit.
2
Edge 1
1 = Signal edge counter 1 has reached its preset limit.
3
Edge 2
1 = Signal edge counter 2 has reached its preset limit.
4
Value 1
1 = Value counter 1 has reached its preset limit.
5
Value 2
1 = Value counter 2 has reached its preset limit.
6…15
Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...