![ABB ACS880-01 Series Firmware Instructions Download Page 377](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621377.webp)
Parameters 377
Selects the communication time levels.
In general, lower time levels of read/write services reduce
CPU load. The table below shows the time levels of the
read/write services for cyclic high and cyclic low data with
each parameter setting.
* Cyclic high data consists of fieldbus Status word, Act1 and
Act2.
** Cyclic low data consists of the parameter data mapped to
parameter groups
and
and acyclic data.
Control word, Ref1 and Ref2 are handled as interrupts
generated on receipt of cyclic high messages.
Normal
Normal speed.
0
Fast
Fast speed.
1
Very fast
Very fast speed.
2
Monitoring
Low speed. Optimized for PC tool communication and
monitoring usage.
3
Activates fieldbus communication monitoring separately for
each control location (see section
on page
).
The parameter is primarily intended for monitoring the
communication with FBA A when it is connected to the
application program and not selected as a control source by
drive parameters.
0000b
0000b…0111b
FBA A communication monitoring selection.
1 = 1
Enables/disables communication between the drive and
fieldbus adapter B, and specifies the slot the adapter is
installed into.
Disable
Communication between drive and fieldbus adapter B
disabled.
0
Option slot 1
Communication between drive and fieldbus adapter B
enabled. The adapter is in slot 1.
1
Option slot 2
Communication between drive and fieldbus adapter B
enabled. The adapter is in slot 2.
2
Option slot 3
Communication between drive and fieldbus adapter B
enabled. The adapter is in slot 3.
3
No.
Name/Value
Description
Def
/
FbEq16
Selection
Cyclic high *
Cyclic low **
10 ms
2 ms
2 ms
10 ms
500 µs
2 ms
250 µs
2 ms
Bit
Name
Value
0
Ext 1
1 = Communication monitoring active when Ext 1 is being used.
1
Ext 2
1 = Communication monitoring active when Ext 2 is being used.
2
Local
1 = Communication monitoring active when local control is being
used.
3…15
Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...