Quadratic
Underload limit is calculated by using the formula:
I
lim
= I
set
* (F
act
/ F
max
)
2
Where,
I
lim
I
set
=
F
max
=
F
act
= Actual speed
User curve
Underload limit depends on the user input load curve, actual
speed/frequency and Underload supervision input.
Defines the source for the supervision signal used in the
underload protection.
NULL
Zero
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
FBA1 ref
3
FBA2 ref
4
EFB1 ref
5
EFB2 ref
6
Estimated motor
current
Parameter
(see page
7
Motor current %
Estimated motor current in % of nominal motor current.
8
). -
Defines underload limit value.
Note:
This parameter is not applicable in case User curve is
selected for the underload curve shape in parameter
0.00
0.00...30000.00
Underload fixed limit.
10 = 1
Selects the type of underload delay time setting.
The user has option to choose between fixed and floating
delay calculation methods.
Constant
Fixed constant value of the delay.
Linear
T
act
= T
set
* (I
act
/ I
lim
)
Where,
T
act
T
set
I
lim
I
act
Quadratic
T
act
= T
set
* (I
act
/ I
lim
)
2
Where,
T
act
T
set
I
lim
I
act
Defines the time used as on-delay for the underload
protection function to react to the underload condition.
10.0
0.0...30000.00 s
Underload delay time in seconds.
1 = 1s
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...