![ABB ACS880-01 Series Firmware Instructions Download Page 309](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621309.webp)
Parameters 309
Defines, together with
, the maximum allowed speed of the motor
or the
estimated speed exceeds the speed limit defined by
parameter
by more than the value of this
parameter, the drive trips on the
fault.
Example:
If the maximum speed is 1420 rpm and speed trip
margin is 300 rpm, the drive trips at 1720 rpm.
500.00 rpm
0.00 … 10000.0
rpm
Overspeed trip margin.
See par.
and
Emergency ramp supervision delay
, together with
, provide a supervision function for
emergency stop modes Off1 and Off3.
The supervision is based on either
• observing the time within which the motor stops, or
• comparing the actual and expected deceleration rates.
If this parameter is set to 0%, the maximum stop time is
directly set in parameter
defines the
maximum allowed deviation from the expected deceleration
rate, which is calculated from parameters
(Off1)
or
(Off3). If the actual
deceleration rate (
) deviates too much from the
expected rate, the drive trips on
, sets bit 8 of
, and coasts to a
stop.
If
is set to 0% and
is set to 0 s, the emergency
stop ramp supervision is disabled.
See also parameter
0%
0…300%
Maximum deviation from expected deceleration rate.
1 = 1%
No.
Name/Value
Description
Def
/
FbEq16
Time
Overspeed trip level
Overspeed trip level
0
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...