![ABB ACS880-01 Series Firmware Instructions Download Page 428](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621428.webp)
428 Parameters
Defines the value for the process 1 feedback and reference
unit scaling.
It is assumed that the process signal might change in range
from 0 to a value set in this parameter. This setting only
serves for rendering process unit to the percent scale and
does not limit the input in any way.
Note:
when this parameter is set to 0, the process 1 feedback
and set point reference scaling is bypassed. The values are
then taken to the process PI controller input.
1000.0
1.00...3000000.00
Process 1 max scale.
10 = 1
Process 1
reference change
rate
Defines the process 1 reference change step.
Together with parameter
desired dynamics for the process 1 reference are defined.
1.00
0.00...100000.00
%/interval
Process 1 reference change rate.
10 =1
%/interval
Defines the process 1 reference step change interval time.
Together with parameter
the desired dynamics for the process 1 reference are
defined.
1.0
0.0...30000.0 s
Process 1 ref step interval.
1 = 1s
Defines the proportional gain setting for the process 1 PI
controller.
1.000
0.000...100000.000 Process 1 control P-gain.
100 = 1
Defines the integration time setting for the process 1 PI
controller.
100.0
0.0...1000000.0 s
Process 1 control I-time.
10 = 1s
Process 2 control
feedback src
Defines the source for the process 2 feedback signal.
See parameter
Process 1 control feedback src
.
Defines the value for the process 2 reference set point.
See parameter
.
0.00
Defines the value for the process 2 feedback and reference
unit scaling.
See parameter
.
100.0
Process 2
reference change
rate
Defines the process 2 reference change step.
Together with parameter
, it
defines the desired dynamics for the process 2 reference.
1.00
0.00...100000.00
%/interval
Process 2 reference change rate.
10 =1
%/interval
Defines the process 2 reference step change interval time.
Together with parameter
, the desired dynamics for the process 2 reference are
defined.
1.0
0.0...30000.0 s
Process 2 ref step interval.
1 = 1s
Defines the proportional gain setting for the process 2 PI
controller.
1.000
0.000...100000.000 Process 2 control P-gain.
100 = 1
Defines integration time setting for the process 2 PI controller. 100.0
0.0...1000000.0 s
Process 2 control I-time.
10 = 1s
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...