Parameters 419
Defines restart delay time.
The timer gets active immediately after stop command is
enabled.
0.0
0.0...30000.0 min
Restart delay time.
10 = 1min
Defines the source for Backspin speed observer function
enable signal.
For further information on Backspin speed observer function,
see section
(page
).
The function detects whether the motor is spinning and
prevents drive start command until passive motor speed
reduces down to speed region defined as safe to restart by
the user.
It is always recommended to enable restart delay and run for
at least several minutes alongside with the backspin speed
observer function.
Not selected
Backspin speed observer function is disabled.
0
Selected
Backspin speed observer function is enabled.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
8
DIO2
Digital input/output DIO2 (
, bit 1).
9
ESP CW bit 2
Parameter
, bit-2 status controls
enable/disable status of the function.
10
).
Defines top negative speed at which fly-start operation is
permitted.
Together with parameter
, safe-
to-restart speed region is formed.
-7.00
-600.00...0.00 Hz
Restart speed limit low.
10 = 1Hz
Defines top positive speed at which fly-start operation is
permitted.
Together with parameter
, safe-
to-restart speed region is formed.
7.00
0.00...600.00 Hz
Restart speed limit high.
10 = 1Hz
Defines the time period required for the motor speed
measured by the Backspin speed observer function to stay
within the safe-to-restart speed region before user-start
command is permitted.
30
0.0...32000.0 s
Observer speed check time.
1 = 1s
Defines the time period required for the Backspin speed
observer function to acquire the estimated motor actual
speed.
The default value should be capable in most of the cases.
5.0
3.0...32000.0 s
Measurement delay.
1 = 1s
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...