374 Parameters
Fault
. This only
occurs if control is expected from the FBA A interface (FBA A
selected as source of start/stop/reference in the currently
active control location), or if supervision is forced using
parameter
1
Last speed
Drive generates an
warning and
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the FBA A interface, or
if supervision is forced using parameter
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe
Drive generates an
warning and
sets the speed to the value defined by parameter
(when speed reference is being used) or
(when frequency reference is being
used). This only occurs if control is expected from the FBA A
interface, or if supervision is forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Fault always
Drive trips on
. This occurs even
though no control is expected from the FBA A interface.
4
Warning
Drive generates an
warning.
This occurs even though no control is expected from the
fieldbus. This only occurs if control is expected from the FBA
A interface, or if supervision is forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
5
Defines the time delay before the action defined by parameter
is taken. Time count starts when
the communication link fails to update the message.
As a rule of thumb, this parameter should be set to at least 3
times the transmit interval of the master.
0.3 s
0.3 … 6553.5 s
Time delay.
1 = 1 s
Selects the type and scaling of reference 1 received from
fieldbus adapter A.
Note:
Fieldbus-specific communication profiles may use
different scalings. For more information, see the manual of
the fieldbus adapter.
Auto
Type and scaling are chosen automatically according to
which reference chain (see settings
,
) the incoming reference is connected to. If the
reference is not connected to any chain, no scaling is applied
(as with setting
0
Transparent
No scaling is applied (the 16-bit scaling is 1 = 1 unit).
1
General
Generic reference with a scaling of 100 = 1 (ie. integer and
two decimals).
2
Torque
The scaling is defined by parameter
.
3
Speed
The scaling is defined by parameter
.
4
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...