![ABB ACS880-01 Series Firmware Instructions Download Page 640](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621640.webp)
640 Fieldbus control through a fieldbus adapter
Setting up the drive for fieldbus control
1. Install the fieldbus adapter module mechanically and electrically according to the
instructions given in the
User’s manual
of the module.
2. Power up the drive.
3. Enable the communication between the drive and the fieldbus adapter module
with parameter
, select how the drive should react to a fieldbus
communication break.
Note:
This function monitors both the communication between the fieldbus
master and the adapter module and the communication between the adapter
module and the drive.
, define the time between communication break
detection and the selected action.
6. Select application-specific values for the rest of the parameters in group
. Examples of appropriate values are
shown in the tables below.
7. Set the fieldbus adapter module configuration parameters in group
. As a minimum, set the required node address and the control profile.
8. Define the process data transferred to and from the drive in parameter groups
.
Note:
Depending on the communication protocol and profile being used, the
Control word and Status word may already be configured to be sent/received by
the communication system.
9. Save the valid parameter values to permanent memory by setting parameter
10. Validate the settings made in parameter groups 51, 52 and 53 by setting
parameter
11. Configure control locations EXT1 and EXT2 to allow control and reference signals
to come from the fieldbus. Examples of appropriate values are shown in the
tables below.
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...