602 Fault tracing
8002
ULC overload fault
Programmable fault:
Selected signal has exceeded
the user overload curve.
See
(page
80A0
AI supervision
Programmable fault:
An analog signal is outside the
limits specified for the analog
input.
Check the auxiliary code (format XXXX
XYZZ). “Y” specifies the location of the
input (
0:
Control unit,
1:
I/O extension
module 1,
2:
I/O extension module 2,
3:
I/O extension module 3). “ZZ” specifies
the limit (
01:
AI1 under minimum,
02:
AI1
above maximum,
03:
AI2 under
minimum,
04:
AI2 above maximum).
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
.
80B0
Signal supervision
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 1 function.
Check the source of the fault (parameter
).
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 2 function.
Check the source of the fault (parameter
).
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 3 function.
Check the source of the fault (parameter
).
9081
External fault 1
(Editable message text)
Programmable fault:
Fault in external device 1.
Check the external device.
Check setting of parameter
.
9082
External fault 2
(Editable message text)
Programmable fault:
Fault in external device 2.
Check the external device.
Check setting of parameter
.
9083
External fault 3
(Editable message text)
Programmable fault:
Fault in external device 3.
Check the external device.
Check setting of parameter
.
9084
External fault 4
(Editable message text)
Programmable fault:
Fault in external device 4.
Check the external device.
Check setting of parameter
.
9085
External fault 5
(Editable message text)
Programmable fault:
Fault in external device 5.
Check the external device.
Check setting of parameter
.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...