302 Parameters
(Only visible when IGBT supply unit control activated by
Displays limit word 4 of the supply unit.
This parameter is read-only.
-
0000h…FFFFh
Supply unit limit word 4.
1 = 1
(Only visible when IGBT supply unit control activated by
Defines a minimum power limit for the supply unit.
Negative values refer to regenerating, ie. feeding power into
the supply network.
-130.0%
-200.0 … 0.0%
Minimum power limit for supply unit.
1 = 1%
(Only visible when IGBT supply unit control activated by
Defines a maximum power limit for the supply unit.
130.0%
0.0 … 200.0%
Maximum power limit for supply unit.
1 = 1%
31
Configuration of external events; selection of behavior of the
drive upon fault situations.
Defines the source of external event 1.
See also parameter
0 = Trigger event
1 = Normal operation
b8)
Active (false)
0.
0
Inactive (true)
1.
1
DIIL
DIIL input (
, bit 15).
2
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
DI6
Digital input DI6 (
, bit 5).
8
DIO1
Digital input/output DIO1 (
, bit 0).
11
DIO2
Digital input/output DIO2 (
, bit 1).
12
Source selection (see
). -
Selects the type of external event 1.
b8)
Fault
The external event generates a fault.
0
Warning
The external event generates a warning.
1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Udc ref max
1 = DC reference is being limited by supply control program
parameters
1
Udc ref min
2
User I max
1 = Current is being limited by supply control program parameters
3
Temp I max
1 = Current is being limited based on temperature
4…15
Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...