Fault tracing 571
A497
Motor temperature 1
(Editable message text)
The thermistor protection
module installed in slot 1
indicates overtemperature.
Check the cooling of the motor.
Check the motor load and drive ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace sensor if faulty.
A498
Motor temperature 2
(Editable message text)
The thermistor protection
module installed in slot 2
indicates overtemperature.
A499
Motor temperature 3
(Editable message text)
The thermistor protection
module installed in slot 3
indicates overtemperature.
A4A0
Control board
temperature
Control unit temperature is
excessive.
Check the auxiliary code. See actions for
each code below.
(none) Temperature above warning
limit
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
1 Thermistor broken
Contact an ABB service representative
for control unit replacement.
A4A1
IGBT overtemperature Estimated drive IGBT
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
A4A9
Cooling
Drive module temperature is
excessive.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See appropriate
Hardware manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
A4B0
Excess temperature
Power unit temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check the auxiliary code (format XXXY
YYZZ). “Y YY” specifies through which
BCU control unit channel the fault was
received. “ZZ” specifies the location (
1:
U-phase,
2:
V-phase,
3:
W-phase,
4:
INT
board,
5:
Brake chopper,
6:
Air inlet
(sensor connected to INT board X10),
7:
PCB compartment fan or power supply
board,
8:
du/dt filter or temperature
switch (XT) (sensor connected to INT
board X7),
9:
Sensor connected to INT
board X6,
0FA:
Ambient temperature).
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...