388 Parameters
Displays a count of packets with a CRC error received by the
drive. An increasing count indicates interference on the bus.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of CRC errors.
1 = 1
Selects how the drive reacts to an EFB communication break.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
No
No action taken (monitoring disabled).
0
Fault
Drive trips on
. This only occurs if
control is expected from the EFB (EFB selected as source of
start/stop/reference in the currently active control location), or
if supervision is forced using parameter
1
Last speed
Drive generates an
warning and
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the EFB, or if
supervision is forced using parameter
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe
Drive generates an
warning and sets
the speed to the speed defined by parameter
(or
when frequency reference
is being used). This only occurs if control is expected from the
EFB, or if supervision is forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Fault always
Drive trips on
. This occurs even though
no control is expected from the EFB.
4
Warning
Drive generates an
warning. This only
occurs if control is expected from the EFB, or if supervision is
forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
5
Defines which message types reset the timeout counter for
detecting an EFB communication loss.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Any message
Any message addressed to the drive resets the timeout.
1
Cw / Ref1 / Ref2
A write of the control word or a reference from the fieldbus
resets the timeout.
2
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...